PH721
The PH721 Balometer Electronic Balancing Tool features a detachable
multi-purpose digital manometer that can be used with a variety
of common test and balance tools, such as pitot, air foil, temperature,
relative humidity probes or a 16-point velocity matrix. It will
become the tool of choice for contractors and facilities personnel
because of its ergonomic design and extremely light weight. |
|
 |
| |
Specifications PH721
| Range |
| diff. pressure |
±15 in. H2O, (3735 Pa) 150 in. H2O
maximum safe operating pressure |
| absolute pressure |
15 to 40 in. Hg (356 to 1016 Hg) |
| velocity |
0.125 to 40 m/s pitot probes;
0.125 to 25 m/s air flow probe;
0.125 to 12.5 m/s velocity matrix; |
| volume |
25 to 2,500 ft3/m (42 to 4250 m3/h) capture hood |
| RH |
0 to 95% RH (optional probe) |
| temperature |
-40 to 121°C probe dependant |
| Resolution |
| pressure |
0.00001 in. H2O (0.001 Pa) Static & Differential Pressure
0.001 in. Hg (1 mm Hg) Absolute Pressure |
| velocity |
0.1 ft/min (0.1 m/s) |
| volume |
0.1 ft3/min (0.1 m3/h) |
| RH |
0.1% RH |
| temperature |
0.1 °C |
| Accuracy |
| pressure |
±2% of reading ±0.025 mm H2O; ±2%
of reading ±0.001 in. Hg |
| velocity |
±3% of reading ±0.04 m/s25 to 8,000 ft/min
(all velocity probes) > 50 ft/min |
| volume |
±3% of reading ±7 ft3 /min 25 to 2,500 ft3/min
> 50 ft/min |
| RH |
±3% RH |
| temperature |
±0.3°C from 0 to 71 °C typically ±0.6°C
from -40 to 0°C and from 71 to 121 °C |
|