ACIN FlowFinder®
The FlowFinder® is an air flow measurement instrument designed
for measurements in mechanical air supply and exhaust systems. The
scales supplied are in dm3/s and m3/h. The operating principle of
the FlowFinder® is based on the zero pressure compensation method.
With this method the resistance of the measuring instrument is compensated
by means of a fan, so the characteristic of the air distribution
system is not influenced by the measurements.
Research at the universities of Stuttgart (D), Trier (D) and Delft
(NL) has proven the zero pressure compensation method to be the
most accurate way of measuring air flows in supply and exhaust ornaments
of various shapes and sizes. |
|
|
| |
Specifications FF225/FF300
| air flow range |
0..225/300 m3/h |
| air temperature range |
-20..+63/83°C |
| inaccuracy @ 20°C |
3..5% of the reading
with minimum value of 2m3/h |
| non-repeatability |
> 1% of the reading |
| battery discharge time |
120/90 min. |
| weight |
3900 g |
| dimensions |
405 x 240 x 225 |
Tab content 4 here